Power · Cooling

Data center power and cooling sizing, from one IT-load target

Enter the IT load and the redundancy target once. DCtoB sizes the UPS, generators, chillers, pumps and cooling units behind it — and keeps every figure in agreement when the load changes.

Data center UPS sizing and selection in DCtoB
UPS selection: modules, parallel sets and redundancy matched to the IT load.

Why power and cooling are sized together

Every kilowatt of IT load needs a path for power to reach it and a path for cooling to remove its heat. The UPS, the generators behind it, the chillers and the pumps are all sized from the same load — plus redundancy. When they are sized in separate spreadsheets, a change to one rarely makes it into the others, and the design stops adding up.

What DCtoB sizes

UPS

Modules, parallel sets and redundancy matched to the IT load and tier target, including distributed-redundant schemes.

Generators

Standby generators for the IT load alone, or for IT and cooling together, sized per block with redundancy.

Chillers & pumps

Chiller and pump selection from the heat load, with the heat-load and flow calculations behind them.

Hydronic loop

Expansion, buffer and make-up vessels sized with the rest of the cooling plant.

Cooling units

CRAHs for air-cooled halls and CDUs for liquid-cooled halls, sized hall by hall.

Mechanical UPS

Continuity power for pumps and cooling units, so cooling rides through the transfer to generators.

Sizing to redundancy, not just to load

Capacity is only half of the answer. The same IT load needs very different equipment depending on whether the target is N+1 or 2N, and whether redundancy is provided by spare modules or by independent paths. DCtoB maps redundancy choices to the Uptime Institute Tier classifications, so N, N+1 and 2N are explicit and consistent across the UPS, generators and cooling plant. N, N+1, 2N and Tier levels explained.

Data center power room layout sized from the IT load in DCtoB
The power block as a dimensioned 2D layout, sized from the same load.

Grounded in recognised standards and real equipment

Equipment is specified and costed from leading vendors — Schneider Electric, Vertiv, Delta, ABB, Eaton, Siemens, Cummins and Caterpillar — and the sized plant flows straight into the single line diagrams and the bill of quantities.

Frequently asked questions

How is UPS capacity sized for a data center?

From the IT load and the redundancy scheme. The load is shared across UPS modules, and redundancy adds capacity on top: N+1 adds a spare module, while 2N duplicates the whole path. DCtoB sizes the modules and parallel sets from your load and tier target.

Does DCtoB size generators for the cooling load too?

Yes. Generators can carry the IT load alone, with cooling on its own generator plant, or carry the combined IT and cooling load — sized per block with the redundancy you set.

Can DCtoB size liquid cooling?

Yes. Liquid-cooled halls are served by CDUs and air-cooled halls by CRAHs, with the chiller plant and hydronic loop sized for both. More on high-density design.

What happens when the IT load changes?

Everything re-sizes from the new target — power, cooling, the single line diagrams, the layout and the cost — because they all read the same model.

See it on a data center of your own

Request a demo to watch DCtoB take a data center from an IT-load target to a costed, standards-aware concept design.